ArmaProtect CT
Cable tube for fire seals in walls and floors
Technical information ArmaProtect CT
Material type
PVC cable tube half shells with intumescent fabric
Additional material information
- Half-shells can be closed with a click lock.
Special features
- Ideal as a retrofitting device.
Property | Value / Assessment | Standard / Test method |
---|---|---|
Operating temperature | ||
Operating temperature | -40°C to 70°C (-40°F to 158°F) | |
Processing Temperature | ||
Processing temperature | 5°C to 25°C (41°F to 77°F) | |
Fire Performance and Approvals | ||
Reaction to fire | Class E | EN 13501-1 |
Use category | Type X: intended for use in conditions exposed to weathering | EOTA TR 024 |
Passive fire protection | ||
Fire resistance of elements of construction | Drywall, concrete wall, aerated concrete wall, masonry wall, concrete floor: up to EI 120
UL approved system: FT-Rating - up to 3 hours | ANSI/UL 1479 (ASTM E814), EN 13501-2 |
Health and environment | ||
Health aspects | Please refer to the safety data sheet available on our website. | |
Emission of dangerous substances | No dangerous substances. | |
Other technical features | ||
Shelf life | No shelf life. | |
Storage | Store / Transport in a cool and dry place with an ambient temperature of 5 °C to 25 °C (41°F to 77°F) and protect from frost. |