Product_Header_1920x384_ArmaFlex

ArmaFlex Protect

Firestop tubes and sheets for fire seals in walls, floors, steel bulkheads and steel decks

Technical information ArmaFlex Protect
Product_pdpImage-800x800_ArmaFlex_Protect_tube

Material type

  • Elastomeric foam based on synthetic rubber.

PropertyValue / AssessmentStandard / Test method
Temperature range
Service temperature
Min. °CMax. °C
-5085
EN 14706, EN 14707, EN 14304
Thermal conductivity
Declared thermal conductivity
Θm0 °C
λd ≤ [W/(m·K)] 0.056
Formulaλd = 0.056 + 0,0001 · ϑm
EN 12667, EN ISO 8497
Fire Performance and Approvals
Reaction to fireE(L) for tubes
E for sheets
EN 13501-1, EN ISO 11925-2
Use categoryType Y2 - intended for use at temperatures below 0 °C, but with no exposure to rain nor UVEOTA TR 024
Fire resistance of bulkhead and decksB-15 bulkheads up to 89 mm
A-60 bulkheads and decks up to 89 mm
IMO 2010 FTP code, Part 3 (IMO A.754(18))
Passive fire protection
Fire resistance of elements of constructionup to EI 120 EN 13501-2, EN 1366-3
Fire performance
Practical fire behaviourSelf-extinguishing, does not drip, does not spread flames
Resistance to water vapour
Water vapour diffusion resistance factorμ ≥ 7,000EN 12086, EN 13469
Health and environment
Volatile organic compounds (VOC) contentFulfills all VOC requirements (French, Italian, Belgian, German AgBB, Blauer Engel and Eurofins Indoor Air Comfort GOLD).ISO 16000 Parts 3, 6 & 9
Health aspectsPlease refer to latest product Safety Datasheet (SDS)
Emission of dangerous substancesNo dangerous substances.
Additional featuresSCCP, MCCP-free
Other technical features
Shelf lifeNo shelf life.
StorageCartons shall be stored horizontally.
Can be stored in dry, clean rooms at normal relative humidity (50 % - 70 %) and ambient temperature (0 °C - 35 °C).
Minimum temperature for transport -50 °C under condition of frost-free storage before installation.