ArmaProtect EFC1 and EFC2
Flexible solution for firestop pipe penetrations
Technical information ArmaProtect EFC1 and EFC2
Material type
Stainless steel strap with self-adhesive flexible
Special features
- Easy visual inspection.
Property | Value / Assessment | Standard / Test method | ||||
---|---|---|---|---|---|---|
Operating temperature | ||||||
Operating temperature | -40°C to 70°C (40°F to 158°F) | |||||
Processing Temperature | ||||||
Processing temperature | 5°C to 25°C (41°F to 77°F) | |||||
Thermal conductivity | ||||||
Declared thermal conductivity |
| |||||
Fire Performance and Approvals | ||||||
Reaction to fire | Class A1 (stainless steel collar) / Class E (intumescent strip) | EN 13501-1 | ||||
Use category | Type Y1: intended for use at temperatures below 0°C with exposure to UV but no exposure to rain | EOTA TR 024 | ||||
Passive fire protection | ||||||
Fire resistance of elements of construction | Drywall, concrete wall, aerated concrete wall, masonry wall: up to EI 120
Concrete floors: up to EI 240 | EN 13501-2 | ||||
Physical attributes | ||||||
Density | 1200 ± 10 kg/m³ | |||||
Mechanical properties | ||||||
Start of reaction / Volume expansion | > 190 °C / 18 to 34 times | |||||
Expansion pressure | > 0.8 N/mm² | |||||
Health and environment | ||||||
Health aspects | Please refer to the safety data sheet available on our website. | |||||
Emission of dangerous substances | No dangerous substances. | ETAG 026-02 | ||||
Other technical features | ||||||
Shelf life | No shelf life. | |||||
Storage | Store / Transport in a cool and dry place with an ambient temperature of 5 °C to 25 °C (41°F to 77°F) and protect from frost. |